Loading documents preview...
HARMONISA
Outline • • • • • • • • • • • •
Introduction THD and TDD Displacement and True Power Factor K-Factor and Transformer Derating When should you be concerned? Application of IEEE 519 Standard Harmonics Measurements Industrial Customers Commercial Customers Revisions to IEEE 519 IEC Standards Conclusions Harmonics
2
What Are Harmonics ? Harmonics are due to distortion of the voltage or current waveform The distortion comes from nonlinear devices, principally loads I(t)
Nonlinear Resistor
V(t)
V I
Harmonics
3
Linear Load
Harmonics
4
Nonlinear Load
Harmonics
5
Harmonic Components 60 Hz (h = 1)
+ +
180 Hz (h = 3) 300 Hz (h = 5)
+ 420 Hz (h = 7)
+ + +
540 Hz (h = 9) 660 Hz (h = 11) 780 Hz (h = 13)
+
· · ·
Harmonics
6
Harmonics
Harmonics
7
Fourier Series Representation • Fourier series
x(t ) co 2
n
sin nt n
n 1
• Average value • RMS Value
C
x co X co2
C n2
n 1
Harmonics
8
Periodical nonsinusoidal waveforms • Most of power voltage and current waveforms have no dc component • Most of normal voltage and current waveforms have no even-order harmonics
Harmonics
9
RMS Values • Under sinusoidal condition:
Vrms Vmax / 2 • Under nonsinusoidal conditions: Vrms
1 T 2 v (t )dt T 0
Harmonics
2 V n n 1
10
Examples 1) x(t ) 100 cos100t X rms 100 / 2 2) x(t ) 100 100 2 cos100t X rms 1002 1002 100 2 3) x(t ) 220 2 cos100t 50 2 cos 300t 2
2
X rms 220 50 .... Harmonics
11
Total Harmonic Distortion Defines the total harmonic content of current or voltage Ratio of the RMS of the harmonic content to the RMS of the fundamental, as % of fundamental
THD (%)
2 V h h2
V1
100%
2 Vrms V12 THD (%) 100% V1 Harmonics
12
Total Demand Distortion Factor (TDD)
Applies for current distortion only. The total rms harmonic current distortion, in % of the maximum demand load current (15 or 30 min demand) 2 I rms I12 TDD(%) 100% I max
Harmonics
13
Harmonic Sources Harmonic sources are nonlinear loads - Saturated transformers and inductors - Switching regulators - Switching power supplies - Variable Speed Drives - Electronic ballast
Harmonics
14
Harmonic Sources
Harmonics
15
Rectifiers AC source
Uncontrolled
DC Load
DC - DC Converter
rectifier
(a) Switched - mode dc power supplies
AC source
Uncontrolled rectifier
PWM Inverter
Induction Motor
(b) Variable - speed AC drives.
AC source
Controlled
PWM Inverter
rectifier
AC Load
(c) Uninterruptible Power Supplies (UPS) Controlled
AC source
DC Load
rectifier
(d) DC power supplies.
AC system
Phase - Controlled rectifier
Phase - controlled inverter
Harmonics (e) DC power transmission systems.
AC system
16
Single-Phase Rectifiers
Harmonics
17
Input Current Harmonics of Single-Phase Rectifiers • The input current has no dc component nor even-order harmonics • The input current harmonic is dominated by the 3-rd order harmonic. • The displacement power-factor is unity but the true-power factor is not unity.
Harmonics
18
Harmonic Profile of Personal Computer
Harmonics
19
Electronic Ballast
Harmonics
20
Electronic ballast Line Current for Electronic Ballast
Current (Amps)
1.00
Max: 0.784 Min: -0.792 Avg: 0.305828 Abs: 0.792 RMS: 0.334094 CF : 2.37059 FF : 1.09242
0.75 0.50 0.25 0.00
-0.25 -0.50 -0.75 -1.00 0
10
20
30
40
50
Time (mS)
Line to Neutral Voltage for Electronic Ballast
200
Max: 170 Min: -170 Avg: 109.055 Abs: 170 RMS: 120.727 CF : 1.40814 FF : 1.10703
Voltage (V)
150 100 50 0 -50 -100 -150 -200 0
10
20
30
40
50
Time (mS)
Harmonics
21
Magnetic Ballast
Harmonics
22
Harmonic Currents in Typical Building
Harmonics
23
DC Drive
Harmonics
24
Three-Phase Rectifier
Harmonics
25
PWM drive, no choke
Harmonics
26
PWM drive with choke
Harmonics
27
Six Pulse Bridge Six pulse bridge - harmonic current 25
20
15 % 10
5
0 1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Harmonic number
Harmonics
28
Input Current Harmonics • The input current has no dc component nor even order harmonics nor multiple three order harmonics. • The existing harmonic order is n 6h 1 • The displacement power-factor is unity but the true power-factor is not unity.
Harmonics
29
What is Power Factor? • Power factor is a measure of how effectively equipment converts or transmits electrical active power at a given rms current and voltage. • Traditionally, the power factor has been defined as the cosine of phase angle difference between voltage and current (displacement power factor). • Apparent power is the maximum active power that can be delivered at a given rms current and voltage. • Power factor is the ratio between the active power to the apparent power (true power factor). • When the harmonics are present, the PF is different to DPF. Harmonics
30
Power Factor
I
V Ip
Iq
0
2
Power Factor POWER
Ip
0
2
Power Factor POWER Iq
0
2
Power Factor
V
IL I1
I5
0
I7
2
Single-Phase Power Concept • Sinusoidal voltage and current
v 2V cos t
i 2 I cost
• Instantaneous power
p vi VI cos 1 cos 2 t VI sin sin 2 t resistive part
Harmonics
reactive part
35
Single-Phase Power Concept • Active or Average Power
1 P T • Reactive Power
t o T
to
pdt VI cos
Q VI sin
• Apparent Power
S VI Harmonics
36
Single-Phase Power Concept • Power triangle 2
2
S P Q
2
• Power factor
P PF cos S Harmonics
37
Single-Phase Power Concept E 2 V V 2 V 2
V 2 V V 2 Thus ΔV E-V RI cos φ XI sin φ RP XQ XQ V V Losses RI 2 R S / V 2
R P /V 2 Q /V 2 Harmonics
38
Single-Phase Power Concept E 2 V V 2 V 2
V 2 V V 2 Thus ΔV E-V RI cos φ XI sin φ RP XQ XQ V V Losses RI 2 R S / V 2
R P /V 2 Q /V 2 Harmonics
39
Balanced Three-Phase Power • Instantaneous power
p va ia vb ib vc ic p 3VI cos • Instantaneous power is a constant that is equal to average power Harmonics
40
Balanced Three-Phase Power • Reactive power is defined as
Q 3VI sin • Apparent power is defined as
S 3VI Harmonics
41
Three-Phase Power System
Harmonics
42
Three-Phase Power System
Harmonics
43
Three-Phase Four-Wire Systems Three - Phase Three - Wire System
Series Losses Considerat ion :
P rs I a2 I b2 I c2 I n2 P
3rs I e2
(unbalanced )
Ie
(balanced)
Ve
I a2 I b2 I c2 I n2 Thus, I e 3 Shunt Losses Considerat ion :
2 2 2 2 Vao Vbo Vco Vno P Rsh
(unbalance d)
Ve2 P 3 Rsh
(balanced)
2 2 2 2 Vao Vbo Vco Vno Thus, Ve 3
or Ve
V
2 an
I V V
2 a
I b2 I c2 / 3
2 an
2 2 Vbn Vcn /3
2 ab
2 2 Vbc Vca /9
2 2 2 2 2 Vbn Vcn Vab Vbc Vca / 12
Apparent Power S e 3Ve I e Power Factor P / S e Harmonics
44
Power concept under nonsinusoidal waveforms
• Voltage
v Vo 2
V
n
cos nt n
n
cos nt n
n 1
• Current
i Io 2
I n 1
• Instantaneous power
p vi Harmonics
45
Power concept under nonsinusoidal waveforms
• Average power
P Vo I o
V I
n n
cos n n
n 1
• Apparent power
S Vrms I rms
• Power factor
P PF S
Vo I o
V I
n n
cos n n
n 1
Vrms I rms Harmonics
46
Reactive Power • What is reactive power under nonsinusoidal conditions? • Some definitions:
Q Vh I h sin h h 1
Q
Vrms I rms
2
P
2
Harmonics
47
Sinusoidal voltage case Average power : Power factor :
P V1 I1 cos1 1
I1 I1 P PF cos1 1 cos 1 1 / 2 S I rms 2 2 In I1 n2 1 1 1
where :
Relationship between power factor and THD:
PF
cos 1 1 THD 2 Harmonics
48
Balanced nonsinusoidal quantities Let assume:
va
Vn cos n t
n 1
For n=1: va1 V1 cost For n=2: va 2 V2 cos 2t For n=3: va 3 V3 cos 3t
vb
Vn cos n t
n 1
vb1 V1 cos t 23
vb 2 V2 cos 2t 23 vb3 V3 cos 3t Harmonics
2 3
vc
n 1
Vn cos n t 23
vc1 V1 cos t 23
vc 2 V2 cos 2t 23
vc 3 V3 cos 3t 49
Balanced nonsinusoidal quantities For n=3k-2, The harmonics are similar to positive sequence quantities. For n=3k-1, the harmonics are similar to negative sequence quantities. For n=3k, the harmonics are similar to zero quantities.
Harmonics
50
Three-Phase Four-Wire System
Harmonics
51
Switched mode power supply currents Phase A (50 Amps)
Neutral (82 Amps)
Phase B (50 Amps)
Phase C (57 Amps)
Harmonics
52
Neutral Current Problem
Neutral Current Problem
Neutral Current Problem
Three-Phase Four-Wire System Phase currents :
iR I h sin ht h h 1
iS I h sin h t 23 h h 1
iT I h sin h t 23 h h 1
Neutral current:
iN iR iS iT 3 I n sin 3ht h n 3 h
Though the phase currents are balanced, the neutral current is not zero if the waveform is nonsinusoidal. The maximum value of neutral current is 1.73 time of phase current. Harmonics
56
Neutral current problems • Neutral current can be excessive • The zero sequence current cannot be detected by overcurrent protection that is located on the primary side. • The transformer losses can be excessive. • The neutral voltage to ground can be excessive. • The size of neutral cable cannot smaller than the phase cables. • Each phase circuit must be provided by separate neutral cable. Harmonics
57
Neutral conductor sizing Neutral currents can easily approach twice the phase currents - sometimes in a half-sized conductor. IEEE 1100-1992 recommends that neutral busbars feeding non-linear loads should have a crosssectional area not less than 173% that of the phase bars. Neutral cables should have a cross-sectional area that is 200% that of the phases, e.g. by using twin single core cables.
Sizing the neutral conductor For three phase circuits using single core cables: • Use a neutral conductor sized for the actual neutral current • If the neutral current is not known, use a double sized neutral cable • Provide overcurrent protection • But take account of the grouping factors! • Take into account voltage drop
Sizing the neutral conductor For multi-core cables : • Multi-core cables are rated for only three loaded cores - applies to both 4 and 5 core cables • When harmonics are present the neutral is also a current carrying conductor • Cable rated for three units of current is carrying more - three phases plus the neutral current • It must be de-rated to avoid overheating • Neutral must have overcurrent protection • Grouping factor must be taken into account
Sizing the neutral conductor - IEC
Neutral conductor protection Neutral conductors should be appropriately sized and provided with over-current protection. The protective device must break all the phases, but does not necessarily need to break the neutral itself. This implies a future need for 4 pole breakers with double rated neutral poles.
Current vs. Voltage Harmonics Distorted Voltage +
Pure Sinusoid
(Voltage Drop)
-
Distorted Load Current
Harmonic currents flowing through the system impedance results in harmonic voltages at the load Harmonics
63
Voltage distortion
Why bother about Harmonics? Important aspect of power quality Damaging Effects to Consumer Loads and Power System Problems may be incipient Non-Linear Loads are Increasing Power Factor Correction Capacitors
Harmonics
65
Capacitors • Shunt capacitor has a significant effect on harmonic levels. • Capacitors do not generate harmonics, but provide network loops for possible resonant conditions. • Resonant frequency:
f res 50 MVAsc / MVAR
Harmonics
66
Series Resonance
Harmonics
67
Parallel Resonance
Harmonics
68
Harmonic Resonance TO POWER SYSTEM
LV
CONVERTOR
M
HARMONICS
AMPLIFIED HARMONICS
Guidelines • • • •
If the KVA of the harmonic producing load is less than 10% of the transformer kVA rating, capacitors can be applied without concern for resonance If the kVA of the harmonic producing load is less than 30% of the transformer kVA rating and the kVAR is less than 20% of the transformer kVA rating, capacitors can be applied without concern for resonance If the kVA of the harmonic producing load is more than 30% of the transformer kVA rating, capacitors should be applied as filters. These guidelines are applicable when transformers with a 5-7% impedance are used and the system impedance behind the transformer is less than 1% of the transformer base.
Harmonics
70
Capacitor standard • • • •
110% of rated rms voltage 120% of rated peak voltage 180% of rated rms current 135% of rated reactive power Including the harmonics
Harmonics
71
Actions must be taken If the limits are exceeded: • Relocation of the capacitors to other parts of the circuit. The harmonic generating loads and the capacitor bank should not share the same transformer. • For wye connected utility transformer banks, the neutral connection to ground may be removed to prevent third harmonics from flowing through the capacitors. • If the above remedies fail, it may be necessary to add a tuning reactor. Harmonics
72
Example (1)
Harmonics
73
Measurement data of example (1)
Harmonics
74
Impedance Seen by The Harmonics
Harmonics
75
Circuit Breakers and Fuses • Currents with 50% distortion factor limited the breaker blowout coil’s ability to force the arc into the arc chute. Vaccum interrupters are less sensitive to harmonic current. • Harmonic distortion affects the current sensing ability of thermal magnetic breakers. • Fuses are not affected by the harmonic content. It should be noted, fuses respond to rms current.
Harmonics
76
Lighting • The incandescent lamp will have a definite loss of life when operated with distorted voltage.
Harmonics
77
Meters • Modern rms meters are relatively immune to the influence of waveform distortion. • Induction disk watthour meter is affected by waveform distortion. The errors vary from 5 to 20%, depending on the harmonic content. This type of meter must be avoided when the harmonic content is high.
Harmonics
78
Digital Meters
Harmonics
79
Digital kWh Meters • For best results, a digital kWh meters must be accurate at least up to 1000 Hz. • The ADC must be at least 12 bit. • By using this specification, it has been shown that the error is less than 1% for current harmonic up to 88 % and voltage harmonic up to 5%.
Harmonics
80
Protective Relaying • In most cases, the waveform distortion of the load current has little effect of the fault current. • Every relay performs differently in the presence of waveform distortion.
Harmonics
81
Rotating Machines • Nonsinusoidal voltages applied to electric machines may cause overheating, pulsating torques, or noise. • Rotoroverheating is the main problem. • For generators, zero sequence current is very dangerous to the rotor.
Harmonics
82
Motor de-rating curve for harmonic voltages 1
De-rating Factor
0.95
0.9
0.85
0.8
0.75
0.7 0
2
4
6 Harmonic Voltage Factor (HVF)
8
10
12
Transformers • The primary effect of power system harmonics on transformers is the additional heat generated by the losses caused by the harmonic content of the load current. • The additional heating caused by harmonics requires load capability derating to remain within the temperature rating of the transformer. • The loading of a delta connected transformer may be misleading because of circulating triplen harmonic currents. Harmonics
84
Transformer Losses • No-load losses or iron losses. These losses can be divided into hysteresis and eddy current losses. These losses almost constant if the voltage is almost sinusoidal. • Load losses. These losses can be divided into I2R loss, eddy current in conductor, and stray losses due to magnetic leakages into the tank, iron core, etc. • The eddy current loss in the conductor is almost proportional to the harmonic frequency. • The stray load losses are usually proportional to fx , where x = 0.8 – 2. Harmonics
85
K-Rating of Transformers Two rating or de-rating systems for transformers:• American system, established by UL and manufacturers, specifies harmonic capability of transformer - known as K factor. • European system, developed by IEC, defines de-rating factor for standard transformers known as factor K.
K-Factor K-Factor is ratio of eddy current losses due to distorted current compared to the losses for the same rms fundamental frequency current Example: Eddy Current Losses with 100 A rms with harmonics = 270 Watts Eddy Current Losses with 100 A rms 60 Hz sine wave = 27 Watts
K - Factor = 270/27 = 10 Harmonics
87
K-Factor
h=
K =
I (pu)
h1
h
Harmonics
2
h
2
88
K-Factor Assumes eddy current losses are proportional to f 2 - OK for small conductor sizes and low harmonics At higher frequencies, eddy current loses are proportional to f Transition frequency depends on winding configuration, material Al - 2200 Hz, Cu - 700 Hz K-factor over estimates harmonics effect at higher frequencies
Harmonics
89
THD and K-Factor Calculation EXAMPLE Fundamental = 10 A rms = 0.96 pu 5th Harm0nic = 2.0 A rms = 0.19 pu 7th Harm0nic = 1.5 A rms = 0.14 pu 11th Harm0nic = 1.0 A rms = 0.096 pu 13th Harm0nic = 1.0 A rms = 0.096 pu Irms = Sqrt (102 + 22 + 1.52 +1.02 + 1.02) = 10.4 A THD = Sqrt (22 + 1.52 + 1.02 +1.02)/10 = 2.87/10 = 28.7 % K = (0.962 + 0.192 * 52 + 0.142 * 72 + 0.0962 *112 + 0.0962*132) = 5.55
Harmonics
90
K-Factor
For this typical PC load, the K factor is 11.6 (See IEE 1100-1992 for a worked example) Harmonics
91
K-Rating of Transformers - US System Next, select a transformer with a higher K rating: standard ratings are 4, 9, 13, 20, 30, 40 and 50.
NB - for non K-rated transformers: The K factor describes the increase in eddy current losses, not total losses.
Transformer Derating Non K-rated transformers have to be derated when load current has harmonics IEEE C57.110 “Recommended Practice for Establishing Transformer Capability When Supplying Nonsinusoidal Load Currents”
Harmonics
93
K-rating K-rated transformers can handle nonsinusoidal load current up to the full load rating with k-factor up to the k-rating of the transformer K-rated transformers are designed to have lower eddy current losses
Harmonics
94
K-Rating of Transformers - European System In Europe, the transformer de-rating factor is calculated according to the formulae in BS 7821 Part 4. The factor K is given by:
e I1 K 1 1 e I
I n q n I1 n2
2 n N
2
0.5
e is ratio of eddy current loss (50 Hz) to resistive loss n is the harmonic order q is dependent on winding type and frequency, typically 1.5 to 1.7
K-Rating of Transformers - European System
For the same PC load, the de-rating factor is 78%
K-Rating or De-rating? ‘K-rated’ transformers are designed to supply harmonic loads by : • using stranded conductors to reduce eddy current losses • bringing secondary winding star point connections out separately to provide a 300% neutral rating
K-Rating or De-rating? ‘De-rating’ a standard transformer has some disadvantages: primary over-current protection may be too high to protect the secondary and too low to survive the in-rush current the neutral star point is likely to be rated at only 100% of the phase current it is less efficient future increases in loading must take the de-rating fully into account
Effect of triple-n harmonics in transformers Triple-n harmonic currents circulate in delta windings they do not propagate back onto the supply network. - but the transformer must be specified and rated to cope with the additional losses.
Skin effect Alternating current tends to flow on the outer surface of a conductor - skin effect - and is more pronounced at high frequencies. At the seventh harmonic and above, skin effect will become significant, causing additional loss and heating. Where harmonic currents are present, cables should be de-rated accordingly. Multiple cable cores or laminated busbars can be used.
Conductors and Cables
Ploss I h2 Rh h 1
Harmonics
101
Conductors and Cables
Ploss
h 1
2 I h Rh
If the skin effect is neglected Ploss
2 RI rms
2 RI1
Harmonics
1 THD
2
102
When Should You be Concerned About Harmonics 20 % of total load is power electronic load If service transformer is loaded near rating When PF correction capacitors are planned Neutral to ground voltage in 120 V supply exceeds 1 to 2 volts
Harmonics
103
Harmonic Standards Several Countries have developed Standards to limit harmonics IEEE 519-1992 IEEE 519A-2004? IEC 61000-3-2, 61000-3-4, 61000-3-12
Harmonics
104
IEEE 519 IEEE 519 “Recommended Practices and Requirements for Harmonic Control in Electric Power Systems” Specifies load current harmonic limits at PCC Specifies supply voltage harmonic limits at PCC IEEE 519A “Guide for Applying Harmonic Limits on Power Systems”
Harmonics
105
IEEE 519 Standard Limits HARMONIC CURRENT DISTORTION LIMITS IN % OF IL V 69 kV ISC / IL 20 20-50 50-100 100-1000 1000
h < 11
11 h 17
17 h 23
23 h 35
35 h
TDD
4.0 7.0 10.0 12.0 15.0
2.0 3.5 4.5 5.5 7.0
1.5 2.5 4.0 5.0 6.0
0.6 1.0 1.5 2.0 2.5
0.3 0.5 0.7 1.0 1.4
5.0 8.0 12.0 15.0 20.0
Harmonics
106
Application Concerns • • • • • •
Selecting PCC Calculating ISC and IL What is TDD ? Measurement Problems Time Varying Harmonics General Procedure for Applying Harmonic Limits • Cost of Problems vs. Cost of Solutions • Distributed Generation Limits Harmonics
107
What is PCC ? “Point in the public network which is closest to the consumer concerned and to which other customers are or may be connected” IEC 61000-34:1998
Harmonics
108
PCC
Harmonics
109
PCC
Harmonics
110
IEEE 519 Standard Limits (Utility) HARMONIC VOLTAGE DISTORTION LIMITS (in % of Nominal Fundamental Frequency Voltage) Bus Voltage at PCC
Individual Harmonic Voltage Distortion
V 69 kV
3.0
69 kV V 161 kV
1.5
2.5
V 161 kV
1.0
1.5
Harmonics
Total Voltage Harmonic Distortion (THDV)
5.0
111
IEEE 519 Standard Limits apply for the “worst case” for normal operation (lasting longer than one hour) For shorter periods, during start-ups limits may be exceeded by 50% Even harmonics are limited to 25% of odd harmonic limits Co-gen - use Isc / IL < 20, irrespective of actual value
Harmonics
112
Harmonic Current Measurements • Calculate harmonics as % of a fixed (average max. demand) current, not as % of fundamental • Limits in the Table Apply only to Odd harmonics – Even Harmonics are limited to 25% of those limits • CT Characteristics are important – usually good (should be less than 3 dB) • How long to monitor? – Very stable, One day may be adequate – one week – for most cases – Permanent monitoring in some cases
Harmonics
113
Presentation of Results – snap shots
Harmonics
114
Presentation of Results – Time Trends
Harmonics
115
Harmonic Voltage Measurements • Measure at PCC • Low Voltage – measure with direct connection • Higher Voltages – Connect with PT – frequency response is good to 3 k Hz (50th harmonic) • Avoid CCVTs – frequency response is not good
Harmonics
116
Evaluation Procedure • Non-linear load is less than 10 - 20% of total plant load – No harmonic evaluation necessary • Weighted Disturbing Power
SDw
(S
Di
Wi )
i
Harmonics
117
T ype of L oad
T y p ic a l W a v e fo rm
C u rre n t D is to rtio n
W e ig h tin g F a c to r (W i)
80% (h ig h 3 rd )
2 .5
1.0
S in g le P h a s e P o w e r S u p p ly
C u r e r n t
0.5
0.0
-0.5
-1.0
0
10
20
30
40
Time (mS) 1.0
0.5
C u r e r n t
S e m ic o n v e rte r
0.0
-0.5
-1.0
0
10
20
30
h ig h 2 n d ,3 r d , 4 th a t p a r tia l lo a d s
2 .5
80%
2 .0
40%
1 .0
28%
0 .8
15%
0 .5
v a rie s w ith firin g a n g le
0 .7
17%
0 .5
40
Time (mS) 1.0
6 P u ls e C o n v e r te r, c a p a c itiv e s m o o th in g , n o s e rie s in d u c ta n c e
C u r e r n t
0.5
0.0
-0.5
-1.0
0
10
20
30
40
Time (mS) 1.0
o n v e r te r, s m o o th in g u c ta n c e > 3 % , d riv e
0.5
C u r e r n t
6 P u lse C c a p a c itiv e w ith s e rie s in d or dc
0.0
-0.5
-1.0 0
10
20
30
40
Time (mS) 1.0
0.5
C u r e r n t
6 P u ls e C o n v e rte r w ith la rg e in d u c to r fo r c u rre n t s m o o th in g
0.0
-0.5
-1.0
0
10
20
30
40
Time (mS) 1.0
1 2 P u ls e C o n v e rte r
C u r e r n t
0.5
0.0
-0.5
-1.0
0
10
20
30
40
Time (mS) 1.0
0.5
C u r e r n t
a c V o lta g e R e g u la to r
0.0
-0.5
-1.0
0
10
20
30
40
Time (mS)
F lu o re s c e n t L ig h tin g
Harmonics
118
Evaluation Procedure • If SDw / Ssc < 0.1%, then automatic acceptance • SDw is weighted disturbing power • Ssc is short circuit capacity at PCC • If customer has or considering PF Correction Capacitors, harmonic evaluation is always necessary
Harmonics
119
UTILITY
CUSTOMER
Choose PCC
Estimate Weighted Disturbing Power (S ) or % Nonlinear DWLoad
Calculate Short Circuit Capacity (I ) SC Is Power Factor Correction Existing or Planned?
Yes
No
Calculate Average Maximum Demand Load Current (I ) L
Stage 1: Is Detailed Evaluation Necessary?
Yes
No
Calculate Short Circuit Ratio (SCR=I /I ) SC L
Characterize Harmonic Levels (Measurements, Analysis)
Stage 2: Does facility meet harmonic limits?
Yes
No
Design Power Factor Correction and/or Harmonic Control Equipment (include resonance and interaction concerns)
Verification Measurements and Calculations (if necessary)
Harmonics
120
Applying Harmonic Limits For Industrial Facilities 1. 2. 3. 4. 5. 6.
Usually supplied by dedicated transformer Several nonliner loads – ASDs, Rectifiers, DC drives, Induction furnaces Loads are relatively low PF - Power factor correction capacitors are installed Industrial loads like motors do not provide much damping for resonance conditions Problems inside the facility before causing problems in utility system Limit Voltage distortion to 5% at PCC – provide some margin for distortion within facility
Harmonics
121
Applying Harmonic Limits For Industrial Facilities 1. 2. 3. 4.
Choose PCC Characterize Harmonic Loads Determine if PF Correction Needed Calculate Expected Current Harmonics at PCC 5. Design Harmonic Control Equipment, if necessary 6. Verify performance with measurements
Harmonics
122
Applying Harmonic Limits For Commercial Customers • Significant percentage of Load is Electronic Equipment and Switch mode Power Supplies • High Efficiency Fluorescent Lighting • HVAC Load is ASD drives • Significant harmonic cancellation -Meeting IEEE 519 at SES is rarely a problem • Internal Harmonic Problems – neutral overheating, transformer overloading, communication interference
Harmonics
123
Overview of Proposed Revisions to IEEE 519 • Immediate – Increased voltage limits for buses < 1 kV – Limits for time-varying harmonics – Revised notch and ringing limits and definitions • Near-term – Measurements • Limits for Single-Phase Equipment – Dropped
Harmonics
124
Voltage Distortion Limits (% of nominal fundamental frequency voltage) B us V o ltag e at P C C (V n )
In d iv id u a l H ar m o n ic V o ltag e D is to rtio n (% )
T o tal V o ltag e D isto rtio n T H D V n (% )
V n 6 9 kV
3 .0
5 .0
6 9 kV V n 1 6 1 kV
1 .5
2 .5
V n 1 6 1 kV
1 .0
1 .5
Harmonics
125
Harmonic Voltage Limits • Add a new voltage limit category for buses less than 1 kV – 5% limit for individual harmonics – 8% limit for voltage THD
• Main concern is associated with multiple zero crossings – Research has shown that concern has merit Harmonics
126
Time-Varying Harmonics • Limits must be based on factual cause/effect – Thermal effects occur over time – Burst distortion effects can be instantaneous – Startup/abnormal conditions should be tolerated • The facts suggest providing – Significant limit increases for short periods – Some limit increases for intermediate periods – No increases for the majority of the time • Some statistical techniques may be needed
Harmonics
127
Time Varying Harmonics (24 hour period) Total Duration of Harmonic Bursts
Maximum Duration of a Single Harmonic Burst
Acceptable Harmonic Distortion Level
<15 minutes
< 15 seconds
3.0 x design limit
>15 minutes and < 1.2 hours
>15 sec and < 30 minutes and
2.0 x design limit
>1.2 hours and
> 30 minutes
design limit
Harmonics
128
Measurements • Define measurement specification – Many commercial meters exist • 8, 12, and 16 cycle windows • 128 and 256 samples/cycle • Filtering
– IEC 61000-4-30 offers potential • Specific requirements • Captures 3s, 10m, and 2hr values
Harmonics
129
IEC Standards Apply at equipment level, 240 V or less, 1-ph, 690 V or less, 3-ph, 50 or 60 Hz 61000-3-2: loads with input current < 16 A 61000-3-12: loads with input current >16A and <75A (published in 2004) 61000-3-4: loads with input current > 75 A Use varies from country to country, mandatory in EC UL certification available in US Harmonics
130
IEC 61000-3-2 Class A - General Purpose loads, 3-ph balanced equipment (plus any eqpt not in B,C,D) Class B - Portable tools Class C - Lighting equipment Class D - Equipment with “special wave shape” (conduction angle < 600), P < 600W Harmonics
131
Class A (Balanced 3-ph Equipment) Harmonic Order 3 5 7 9 11 13 15-39 2 4 6 8-40
Max. Permissible Harmonic Current (Amps) 2.3 1.14 0.77 0.4 0.33 0.21 0.15 x 15/n 1.08 0.43 0.30 0.23 x 8/n Harmonics
132
Class C Equipment (Lighting >25W) Harmonic Order
Max. Harmonic Current (% of Fund.)
2 3 5 7 9 11-39
2 30 x PF 10 7 5 3
(odd harmonics only)
Harmonics
133
Class D Equipment (Special Waveshape) Harmonic Order
Relative Limit (mA/W)
3 5 7 9 11 13-39
3.4 1.9 1.0 0.5 0.35 3.85/n
Max. Harmonic Current (Amps) 2.30 1.14 0.77 0.40 0.33 0.15 x 15/n
(odd harmonics only)
Harmonics
134
IEC 3-12 (for Equpt >16 A and < 75 A)
Harmonics
135
IEC 61000-3-4 Loads with rated current > 75 A
Stage 1: SC KVA/EQ. KVA > 33 Stage 2: SC KVA/EQ. KVA 66, 120, 175, 250, 350, 450, 600 Stage 3: Local Utility Requirements apply. Harmonics
136
IEC Standards IEC Standards are based on European distribution system 3 ph, 3-wire feeder, and 3-ph, 3-wire branches, 11 or 12 kV 3-ph (delta-star), large (500 kVA - 1000 kVA) distribution transformers 400/230V, 3-ph long secondary USNC - IEC standards in US Harmonics
137
US distribution systems are different 3-ph, 4-wire Feeder, 1-ph, 2-wire branches, most 15 kV class Small (50 - 100 kVA) transformers serving 6 to 8 residents 120/240 V, 1-ph, short secondaries No consensus between manufacturers, utilities and users Harmonics
138
Comparison of European and North American Systems European
North American
Feeder
3-ph, 3-wire
3-ph, 4-wire
Branch
3-ph, 3-wire
1-ph, 2-wire
Transformer 500 kVA-1MVA 50 kVA-100kVA Connection
Y/
Secondary
400/230V, 3-ph 120/240V, 1-ph
Length
Long
Gr Y / Gr Y short
Harmonics
139
Harmonic Mitigation Techniques • Harmonic Source Side • Medium side • Equipment side
Harmonics
140
Harmonic Source side • Multipulse rectifiers • PWM rectifiers • Unity power-factor rectifiers
Harmonics
141
12-Pulse Rectifier
Harmonics
142
12-Pulse Bridge Twelve pulse bridge - harmonic current 25
20
15 % 10
5
0 1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Harmonic number
Harmonics
143
6N-Pulse Rectifier
Harmonics
144
Multipulse Rectifiers
Harmonics
145
Unity Power Factor Rectifier
Harmonics
146
Three-Phase Unity Power Factor Rectifier
Harmonics
147
Single-Phase PWM Rectifier • Bidirectional power flow • The input power factor is adjustable • The input current waveform is adjustable
Harmonics
148
Three-Phase PWM Rectifier
Harmonics
149
Medium side • Passive filters • Active filters • Combination of active and passive filters
Harmonics
150
Harmonic reduction transformers
Load I3 Interconnected Star Transformer sized for harmonic currents only
Isolating transformers Delta-star isolating transformers reduce propagation of harmonic current into the supply. Transformers should be adequately rated to cope with the harmonics Although the transformer effectively establishes a new neutral, don’t use half-sized neutrals Provide a well rated four wire feed so that the transformer can be isolated for service
Isolating transformers
Isolating transformers
Isolating transformers
Isolating transformers
Parallel Passive Filters
Harmonics
157
Series Passive Filters
Harmonics
158
Passive harmonic filters Filters are useful when the harmonic profile is well defined – such as motor controllers the lowest harmonic is well above the fundamental frequency - but filter design can be difficult and, especially for lower harmonics, the filters can be bulky and expensive
Active filters Where the harmonic profile is unpredictable or contains a high level of lower harmonics, active filters are useful Active harmonic conditioners operate by injecting a compensating current to cancel the harmonic current
Filters are useful when the harmonic profile is well defined – such as motor controllers the lowest harmonic is well above the fundamental frequency - but filter design can be difficult and, especially for lower harmonics, the filters can be bulky and expensive
Harmonics
161
Series Active Filters
Harmonics
162
Parallel-Passive Parallel-Active
Harmonics
163
Series-Active Series-Passive
Harmonics
164
Series-Active Parallel-Passive
Harmonics
165
Series-Passive Parallel-Active
Harmonics
166
Series Parallel-Passive Parallel-Active
Harmonics
167
Parallel Series-Passive Series-Active
Harmonics
168
Comparison of hybrid filters
Harmonics
169
Equipment side • K rated transformers • Generator derating • Cable derating
Harmonics
170
Reducing Voltage Distortion by Circuit Separation
Harmonic solutions Keep circuit impedances low Rate neutrals and multi-core cables generously 1.73 to 2 times normal size Always use true RMS meters Provide a large number of separate circuits to isolate problem and sensitive loads Take harmonics into account when rating transformers Provide appropriate filtration where required
Conclusions • Harmonics are important aspect of power quality • Application of power electronics is causing increased level of harmonics • Survey the loads and make preliminary evaluation • IEEE and IEC Standards reviewed Harmonics
173