ETAP Knowledge Base
Low Voltage Breaker Typical Operating Time Description: Typical operating times for low voltage circuit breakers Category:
LV CB, Operating Times
Type:
Information
Keywords:
Typical Operating Times, low voltage circuit breaker
Typical operating times for low voltage circuit breakers are listed in the following table: Table1 of IEEE 1584 2002: Power Circuit Breaker Operating Timesa Circuit Breaker Rating and Type Molded Case (<1000 V) (Integral Trip) Insulated Case (<1000 V) (Integral Trip or relay operated) Power CB (<1000) (Integral Trip or relay operated)
Opening Time at 60 Hz (Cycles) 1.5
Opening time at 50 Hz (Cycles) 1.25
Opening Time in Seconds
3.0
2.5
0.050
3.0
2.5
0.050
0.025
a
All the values listed in this table do not include the external trip times.
This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by Operation Technology, Inc. All Rights Reserved.